CS multi channel display and recorder DS 300

Wednesday, 16 March 2011 09:36
Inquiry
Download attachments:
CS multi channel display and recorder DS 300

DS 300 is a multifunction measurement instrument for industrial applications. The base unit consists of a LCD graphics display, 2 relay outputs, USB interface in a panel/wall mountable casing. Through various options DS 300 can be configured to specific customer requirements. These options include: data recording, RS-485-interface, sensor inputs for CS flow and dew point sensors, sensor inputs for process signals (0-1V, 0-10V, 0-20 mA, 4-20mA) and temperature sensors (thermocouples, Pt100, Pt1000).







Industrial communication

Measurement in industrial environment often lacks of convenient acquisition and monitoring. The operator would like to have all measurement values on the screen in the office area rather than walking from one instrument to the other to get the readings. CS is offering various solutions to bring information from the factory to the office. Basically DS 300 supports following filedbus options:

RS-485-Bus
RS-485 bus is commonly used in industrial applications. It can reach up to 1000 m distance with a shielded twisted pair cable. If further distance is required, a repeater can be installed to reach another 1000 m. For the communication protocol the user can select CSBus (internal CS protocol for CS-Monitor software) or Modbus for third party software (SCADA). Through a RS-485 / USB converter the system is connected to a USB port of the office PC.

Ethernet
Since Ethernet is commonly available in offices it becomes more and more poplar in industrial environment as well. DS 300 can be connected to an Ethernet switch or router and through the software CS-Monitor (CSM-S or CSM-M) accessed as if DS 300 would be connected directly to an USB port at the PC.

Please find more information about DS 300 and industrial communication in this document: “I
nstruction manual_DS 300 Communication"


 

Features:

  • Wall or panel mountable
  • Universal power supply 100...240 VAC
  • Big graphic display
  • 2 relay (240 VAC, 3A)
  • 2 inputs for CS flow dew point sensors
  • Up to 4 sensors connctable
  • Programmable alarm
  • Options:
  • Data logger
  • RS-485 interface for CSBus or Modbus
  • Ethernet
 

Technical Data:

Technical data DS 300
Casing

Size: 118x115x93mm
Panel size: 92x92
Protection class: IP65

Power supply
100...240 VAC, 50-60 Hz, 40 VA
InterfaceUSB to PC
Alarm output
2 relay, 230 VAC, 3 A
Ambient conditions
0 ... 50 ºC
Sensor inputs 
(up to channels)
A:  2 channel SDI:
         FA 300, FA 4xx
         VA 300, VA 4x0
B:  2 channel analogue:
         0-1V, 0-10V
         0-20 mA, 4-20 mA
         Pt100/Pt1000
Accuracy 1)Dew point:         See sensor specs.
Flow:                 See sensor specs.
0-20 mA:           0.01 mA
0-10 V:              0.01 V
Pt100:                0.2 ºC
Pt1000:              0.2 ºC
Analogue outputs
4-20 mA and pulse signals from sensors accessible at rear connectors
Data loggerUp to 1,000,000 values
RS-485
Up to 32 DS300 can be connected together and linked to a computer
1) Accuracy of sensor not included
 

Application:

alt  alt
 Dew point display  Stationary flow station
 

Order. No:

Order No.Description
0500 3000
Base unit, 100...240 VAC, 50-60 Hz, wall casing
0500 3100
Base unit, 100...240 VAC, 50-60 Hz, wall casing, logger function
A1030
2 input channels for CS sensors [FA 400, VA 400]
A1031
2 input channels for CS sensors [FA 400, VA 400] + RS-485 [CSBus / Modbus]
A1032
RS-485 [no SDI input]
A1034
2 input channels for CS sensors [FA 400, VA 400] + Ethernet
A1033
Analogue input, 2 channels [0-20 mA, 0-10 V, Pt 100, Pt 1000]

Order No.Description
0554 0013Modbus / Ethernet gateway
0554 0011
RS-485 Repeater, hat rail mountable
0554 0006
Power supply for gateway, hat rail moutable
0554 7010
CSM-S software for DS 300 + DS 300 Configuration software, including USB cable
0990 0010
Plug&Play option: Complete wired (5m sensor cable and mains plug), programmed accroding to your order
0599 7010
CSM-S Software license
0599 2020
CS-Monitor CSM-M Basic package up to 5 DS 300
0599 2021
CS-Monitor CSM-M Basic package up to 10 DS 300
0599 2022
CS-Monitor CSM-M Basic package up to 20 DS 300
0599 2023
CS-Monitor CSM-M Basic package up to 30 DS 300
A1101
Consumption report generator for CSM-M
0554 0331
USB / RS-485 converter

 
Last modified on Thursday, 17 November 2011 08:45
We are here to help. Click here to submit your Inquiry

 

Testimonials

By monitoring our compressed air system with CS Products and implementing improvements we achieved a costs saving of 20%.

- Li Gou Fu, Facility Manager, Fuji Electric